Scaling model study of the air distribution in a powerhouse under different ventilation conditions

Pengfei Tao1Angui Li1( )Jianfei Zhang2Jianming Wang3
School of Environmental and Municipal Engineering, Xi’an University of Architecture and Technology, Xi’an 710055, China
No.6 Institute of Project Planning & Research of Machinery Industry, China
Beijing State Power of Hydraulic and Electric Engineering Co., Ltd, Beijing 100024, China
Show Author Information

Abstract

In order to clarify the air temperature distribution and air velocity distribution of a hydroelectric generating powerhouse in the mechanical ventilation mode, detailed ventilation experiments were conducted using a 1:20 small-scale model of a pumped-storage hydroelectric power station. In this model, we arranged fifty-seven circular inlets in double and triple rows to simulate the air supply pattern in a typical powerhouse. Six combinations of the inlets, and three air supply rates (28 m3/h, 56 m3/h, and 112 m3/h) were selected to determine the effect of the inlets’ arrangement and the air supply rates on the air distribution in the occupied zone of the powerhouse. A dimensionless method was adopted to process the acquired data of the air temperature and air velocity. The results revealed that the inlets’ arrangements and the air supply velocity had a significant influence on the air distribution in the powerhouse. Simultaneously, the ventilation efficiency of four heat sources was studied in the optimum case, i.e. the most effective air supply rate is 112 m3/h among the three tested values. The results of the experiments revealed that the air distribution was nearly independent of adjustable heat release rates. Our findings in this work may offer a significant advance in the understanding of ventilation system designs for hydroelectric powerhouses.

References

 
X Chang, X Liu, W Zhou (2010). Hydropower in China at present and its further development. Energy, 11: 4400-4406.
 
Q Chen (2009). Ventilation performance prediction for buildings: A method overview and recent applications. Building and Environment, 44: 848-858.
 
Q Chen, K Lee, S Mazumdar, S Poussou, L Wang, M Wang, Z Zhang (2010). Ventilation performance prediction for buildings: Model assessment. Building and Environment, 45: 295-303.
 
W Chow, L Wong, W Fung (2002). Preliminary studies on a new method for assessing ventilation in large spaces. Building and Environment, 37: 145-152.
 
DL/T 5165-2002 (2002). Design code for heating ventilation and air conditioning of power house of hydropower station.
 
H Huang, Z Yan (2009). Present situation and future prospect of hydropower in China. Renewable and Sustainable Energy Reviews, 13: 1652-1656.
 
A Li, Z Liu, J Zhang, J Wang (2011). Reduced-scale model study of ventilation for large space of generatrix floor in Hohhot underground hydropower station. Energy and Buildings, 43: 1003-1010.
 
A Li, E Qin, B Xin, G Wang, J Wang (2010). Experimental analysis on the air distribution of powerhouse of Hohhot hydropower station with 2D-PIV. Energy Conversion and Management, 51: 33-41.
 
A Li, P Tao, A Bao, Y Zhao (2013). PIV measurements of air distribution in a reduced-scale model—Ventilation of a busbar corridor in a hydropower station. International Journal of Ventilation, 12: 81-98.
 
M Woloszyn, C Rode (2008). Tools for performance simulation of heat, air and moisture conditions of whole buildings. Building Simulation, 1: 5-24.
 
Y Xiao, X Liu, R Zhang (2012). Calculation of transient heat transfer through the envelope of an underground cavern using Z-transfer coefficient method. Energy and Buildings, 48:190-198.
 
Y Yu, X Li, W Shi (2009). A simplified model of heat and moisture transfer for tailrace tunnel ventilating in hydropower station. Applied Thermal Engineering, 29: 3254-3260.
 
I Yüksel (2010). Hydropower for sustainable water and energy development. Renewable and Sustainable Energy Reviews, 14: 462-469.
Building Simulation
Pages 389-400
Cite this article:
Tao P, Li A, Zhang J, et al. Scaling model study of the air distribution in a powerhouse under different ventilation conditions. Building Simulation, 2014, 7(4): 389-400. https://doi.org/10.1007/s12273-013-0155-2

498