Research Article

Air and air contaminant flows in office cubicles with and without personal ventilation: A CFD modeling and simulation study

Meng Kong( )Jianshun ZhangJingjing Wang
Department of Mechanical Engineering, Syracuse University, 263 Link Hall, Syracuse, NY 13244, USA
Show Author Information

Abstract

The paper is aimed at building an appropriate computational fluid dynamics (CFD) model for simulating the flow field in the office cubicle with and without personalized ventilation (PV) and using it to investigate the flow field in the cubicle. A computational model was first constructed by using a commercial CFD code (STAR-CCM). In this process, different approaches to represent manikins, boundary conditions, geometries, and gridding were tested, and a proper approach was selected for simulating the air and contaminant movement in the cubicles and their interactions with the remaining room space. A comparison between the simulation and the experimental results are made to show how accurate the CFD model can be. A brief evaluation of the environmental quality was conducted for both cases with PV and underfloor air diffuser (UFAD). This comparison showed a significant advantage in the PV system, indicating how the PV system performed under different airflow rates. This verified CFD model will be utilized in the future to investigate the performance of the partitioned cubicle collaborating with personalized ventilation systems.

References

 
R Cermak, AK Melikov, L Foreijt, O Kovar (2011). Performance of personalized ventilation in conjunction with mixing and displacement ventilation. HVAC&R Research, 12: 295-311.
 
Q Chen, W Xu (1998). A zero-equation turbulence model for indoor air flow simulation. Energy and Building, 28: 137-144.
 
M Chludzinska, A Bogdan (2008). Individual ventilation—Users' whim or economically justified energy saving. Ciepłownictwo, Ogrzewnictwo, Wentylacja, 2: 32-34 (in Polish).
 
T Dang (2008). Personalized ventilation system using combined jet nozzle and flow suction. US Provisional Patent No. 61/022956.
 
M Deevy, Y Sinai, P Everitt, L Voigt, N Gobeau (2008). Modelling the effect of an occupant on displacement ventilation with computional fluid dynamics. Energy and Buildings, 40: 255-264.
 
RK Dygert, TQ Dang (2012). Experimental validation of local exhaust strategies for improved IAQ in aircradt cabins. Building and Environment, 47: 76-88.
 
RK Dygert, JS Russo (2009). Modeling of the human body to study the personal micro environment. ASHRAE Transactions, 115(2): 407-420.
 
N Gao, J Niu (2004). CFD study on mocro-environment around human body and personalized ventilation. Building and Environment, 39: 795-805.
 
N Gao, J Niu (2005). Modeling the performance of personalized ventilation under different room airflows. In: Proceedings of IBPSA International Conference, Montreal, Canada.
 
N Gao, J Niu (2006). Transient CFD simulation of the respiration process and interperson exposure assessment. Building and Environment, 41: 1214-1222.
 
T Hayashi, Y Ishizu, S Kato, S Murakami (2002). CFD analysis on characteristics of contaminated indoor air ventilation and its application in the evaluation of the effects of contaminant inhalation by a human occupant. Building and Environment, 37: 219-230.
 
Y Houdas, E Ring (1982). Human Body Temperature: Its Measurement and Regulation. New York: Plenum Press.
 
ISO 14505-2. (2006). Ergonomics of the thermal environment—Evaluation of the thermal environments in vehicles—Part 2: Determination of equivalent temperature. ISO Standard.
 
J Kaczmarczyk, AK Melikov, PO Fanger (2004). Human response to personalized ventilation and mixing ventilation. Indoor Air, 14(suppl 8): 17-29.
 
EH Khalifa, MI Janos, JF Dannenhoffer (2009). Experimental investigation of reduced-mixing personal ventilation jets. Building and Environment, 44: 1551-1558.
 
EH Khalifa, SJ Prescod, JF Dannenhoffer, B Elhadidi (2006). Computation of occupant exposure in an office cubicle. In: Proceedings of AWMA/EPA Conference: Indoor Air Quality—Problems, Research and Solutions, Durham, USA.
 
AK Melikov (2004). Improving comfort and health by personalized ventilation. In: Proceedings of Roomvent 2004, Coimbra, Portugal.
 
AK Melikov, R Cermak, M Majer (2002). Personalized ventilation: Evaluation of different air terminal devices. Energy and Building, 34: 829-836.
 
AK Melikov, V Dzhartov (2013). Advanced air distribution for minimizing airborne cross-infection in aircradt cabin. HVAC&R Research, 19: 926-933.
 
PV Nielsen, E Barszcz, T Czarnota, DP Dymalski, MA Jasienski, A Nowotka, A Nowotka, A Mozer, SM Wiankowska, RL Jensen (2008). The influence of draught on a seat with integrated personalized ventilation. In: Proceedings of Indoor Air 2008, 11th International Conference in Indoor Air Quality and Climate, Copenhagen, Denmark.
 
PV Nielsen, NM Bartholomaeussen, E Jakubowska, H Jiang, OT Jonsson, K Krawiecka, A Mierzejewski, SJ Jessica, K Trampczynska, M Polak, M Soennichsen (2007a). Chair with integrated personalized ventilation for minimizing cross infection. In: Proceedings of Roomvent 2007, 10th International Conference on Air Distribution in Rooms, Helsinki, Finland.
 
PV Nielsen, C Damsgaard, L Liu, RL Jensen (2013). Test of different air distribution concepts for a single-aisle aircraft cabin. In: Proceedings of CLIMA 2013, Prague, Czech Republic.
 
PV Nielsen, CE Hyldgard, A Melikov, H Andersen, M Soennichsen (2007b). Personal exposure between people in a room ventilated by texile terminals: with and without personalized ventilation. HVAC&R Research, 13: 635-644.
 
PV Nielsen, H Jiang, M Polak (2007c). Bed with integrated personalized ventilation for minimizing cross infection. In: Proceedings of Roomvent 2007, 10th International Conference on Air Distribution in Rooms, Helsinki, Finland.
 
HO Nilsson, I Holmér (2004). Comfort climate evaluation with thermal manikin methods and computer simulation models, Indoor Air, 13: 28-37.
 
JS Russo (2010). A detailed and Systematic Investigation of Personal Ventilation Systems. Phd Dissertation, Syracuse University.
 
JS Russo, TQ Dang, EH Khalifa (2009). Computational analysis of reduced-mixing personal ventilation jets. Building and Environment, 44: 1559-1567.
 
STAR-CCM. (2012). Tutorial Guide of STAR-CCM.
 
JA Vander, HJ Sherman, SD Luciano (1994). Human Physiology: The Mechanisms of Body Function. New York: McGraw-Hill.
 
G Villi, MC Carli (2014). Detailing the effects of geometry approximation and grid simplification on the capability of a CFD model to address the benchmark test case for flow around a computer simulated person. Building Simulation, 7: 35-55.
 
W Xu, Q Chen (2000). Simulation of mixed convection flow in a room with a two-layer turbulence model. Indoor Air, 10: 306-314.
 
W Xu, Q Chen (2001). A two-layer turbulence model for simulating indoor airflow Part II. Applications. Building and Environment, 33: 627-639.
 
R Zhuang, X Li, J Tu (2014). CFD study of the effects of furniture layout on indoor air quality under typical office ventilation schemes. Building Simulation, 7: 263-275.
Building Simulation
Pages 381-392
Cite this article:
Kong M, Zhang J, Wang J. Air and air contaminant flows in office cubicles with and without personal ventilation: A CFD modeling and simulation study. Building Simulation, 2015, 8(4): 381-392. https://doi.org/10.1007/s12273-015-0219-6