Research Article

An evaluation index for the control effect of the local ventilation systems on indoor air quality in industrial buildings

Yi Wang1( )Yingxue Cao1Bo Liu1Jiaping Liu1Yang Yang1Qun Yu1,2
School of Environmental and Municipal Engineering, Xi'an University of Architecture and Technology, No. 13 Yanta RD., Xi'an, Shaanxi 710055, China
Shaanxi Architectural Design and Research Institute, China
Show Author Information

Abstract

To evaluate the control effect on indoor air quality (IAQ) of the local ventilation systems in industrial buildings with centralized contaminant sources, a new index, namely, normalized concentration in the target zone (NC-TZ), was proposed in this paper. According to theoretical analysis, NC-TZ is non-dimensional and ranges from 0 to 1. When NC-TZ tends toward 0, the control effect of the local ventilation system on IAQ is more satisfactory. When NC-TZ tends toward 1, the control effect on IAQ is less satisfactory. The numerical simulation on a push-pull ventilation system with varying exhaust flow rates and varying distances between push and pull hoods was performed. The results demonstrate that for the same capture efficiency, changing the local ventilation system characteristics can change the control effect on the local environment. The results for obstacles at different positions also indicate that NC-TZ can clearly reflect the control effect on IAQ of the local ventilation systems in industrial buildings.

References

 
M Brown (2006). Making sense of modernity's maladies: Health and disease in the industrial revolution. Endeavour, 30: 108-112.
 
G Cao, K Sirén, S Kilpeläinen (2014). Modelling and experimental study of performance of the protected occupied zone ventilation. Energy and Buildings, 68: 515-531.
 
S-J Cao, J Meyers (2015). Fast prediction of indoor pollutant dispersion based on reduced-order ventilation models. Building Simulation, 8: 415-420.
 
Q Chen (1995). Comparison of different k-ε models for indoor air flow computations. Numerical Heat Transfer, Part B: Fundamentals, 28: 353-369.
 
BJ Divine, CM Hartman (2001). A cohort mortality study among workers at a 1,3 butadiene facility. Chemico-Biological Interactions, 135-136: 535-553.
 
D-H Koh, T-W Kim, Y-H Yoon, K-S Shin, S-W Yoo (2011). Lymphohematopoietic cancer mortality and morbidity of workers in a refinery/petrochemical complex in Korea. Safety and Health at Work, 2: 26-33.
 
MJ Ellenbecker, RF Gempel, WA Burgess (1983). Capture efficiency of local exhaust ventilation systems. American Industrial Hygiene Association Journal, 44: 752-755.
 
R Howell, T Hayashi, M Shibata, K Tsuji (1985). Industrial Ventilation and Air Conditioning. Boca Raton, FL, USA: CRC Press.
 
S Kikuchi, K Ito, N Kobayashi (2003). Numerical analysis of ventilation effectiveness in occupied zone for various industrial ventilation systems. In: Proceedings of 7th International Symposium on Ventilation for Contaminant Control, Sapporo, Japan, pp. 103-108.
 
S Kikuchi, K Ito, N Kobayashi (2004). Study on normalized concentration in an occupied zone in office space. In: Proceedings of 9th International Conference on Air Distribution in Rooms, Coimbra, Portugal.
 
M Lateb, C Masson, T Stathopoulos, C Bédard (2013). Comparison of various types of k-ε models for pollutant emissions around a two-building configuration. Journal of Wind Engineering and Industrial Aerodynamics, 115: 9-21.
 
Y Li, PV Nielsen (2011). Commemorating 20 years of indoor air CFD and ventilation research. Indoor Air, 21: 442-453.
 
U Madsen, NO Breum, PV Nielsen (1994). Local exhaust ventilation—A numerical and experimental study of capture efficiency. Building and Environment, 29: 319-323.
 
A Makhoul, K Ghali, N Ghaddar (2013). Desk fans for the control of the convection flow around occupants using ceiling mounted personalized ventilation. Building and Environment, 59: 336-348.
 
J Ojima (2002). Worker exposure due to reverse flow in push-pull ventilation and development of a reverse flow preventing system. Journal of Occupant Health, 44: 391-397.
 
M Robinson, DB Ingham (1996). Recommendations for the design of push-pull ventilation systems for open surface tanks. Annals of Occupational Hygiene, 40: 693-704.
 
M Sandberg (1981). What is ventilation efficiency? Building and Environment, 16: 123-135.
 
M Sandberg (1983). Ventilation efficiency as a guide to design. ASHRAE Transactions, 89(2): 455-479.
 
M Sandberg, M Sjoberg (1983). The use of moments for assessing air quality in ventilated rooms. Building and Environment, 18: 181-197.
 
J Sundell (1996). What we know, and don't know about sick building syndrome. ASHRAE Journal, 38(6): 51-57.
 
P Wargocki, DP Wyon, YK Baik (1999). Perceived air quality, sick building syndrome (SBS) symptoms and productivity in an office with two different pollution loads. Indoor Air, 9: 165-179.
 
JE Woods (1989). Cost avoidance and productivity in owning and operating buildings. State of the Art Reviews in Occupational Medicine, 4: 753-770.
 
H Xing, A Hatton, HB Awbi (2001). A study of the air quality in the breathing zone in a room with displacement ventilation. Building and Environment, 36: 809-820.
 
B Zhao, X Li, D Li, J Yang (2003). Revised air-exchange efficiency considering occupant distribution in ventilated room. Journal of the Air & Waste Management Association, 53: 759-763.
Building Simulation
Pages 669-676
Cite this article:
Wang Y, Cao Y, Liu B, et al. An evaluation index for the control effect of the local ventilation systems on indoor air quality in industrial buildings. Building Simulation, 2016, 9(6): 669-676. https://doi.org/10.1007/s12273-016-0295-2