Research Article

Numerical study on the effect of elevator movement on pressure difference between vestibule and living room in high-rise buildings

Younggi Park1Junyoung Na1Kun Hyuk Sung2Hong Sun Ryou1( )
Department of Mechanical System Engineering, Chung-Ang University, 221 Heukseok-dong, Dongjak-gu, Seoul, 156-756, R.O. Korea
Department of Mechanical Engineering, Chung-Ang University, 221 Heukseok-dong, Dongjak-gu, Seoul, 156-756, R.O. Korea
Show Author Information

Abstract

In this study, we experimentally and numerically investigated the effect of elevator movement on the pressure difference between vestibule and living room regulated by the smoke control system in a high-rise building. The elevator and smoke control systems using supplied pressure dampers are considered one of the most important systems for safe evacuation. However, the pressure field and flow rate are strongly disrupted by elevator movement. Thus, they can affect the performance of smoke control systems and hinder evacuation. The experimental results of this study are used to validate the results of the numerical study when elevator is moving at low speed or is stationary. Then, the effect of elevator movement on the pressure difference between the vestibule and living room, which is controlled by the smoke control system, is investigated numerically using ANSYS CFX. The elevator speed is increased from 10 to 70 m/s, corresponding to the real elevator speed increase of 1.5 to 10 m/s based on Reynolds similarity. It is found that the higher the elevator speed, the greater the pressure difference between the vestibule and living room. This shows that the airflow rate should be actively changed by considering the location of the elevator and its speed. The empirical correlation between elevator movement and pressure difference is derived.

References

 
J Averill, D Mileti, R Peacock, E Kuligowski, N Groner, G Proulx, P Reneke, H Nelson (2005). Federal building and fire safety investigation of the world trade center disaster—Occupant behavior, egress and emergency communications. NIST NCSTAR 1-7. Washington DC: US Government Printing Office.
 
WZ Black (2011). Computer modeling of stairwell pressurization to control smoke movement during a high-rise fire. ASHRAE Transactions, 117: 786–800.
 
R Bukowski (2008). Status of the Use of Elevators in Fires. Society of Fire Protection Engineers.
 
SCP Cheung, SM Lo, GH Yeoh, RKK Yuen (2006). The influence of gaps of fire-resisting doors on the smoke spread in a building fire. Fire Safety Journal, 41: 539–546.
 
S-W Chien, W-J Wen (2011). A research of the elevator evacuation performance and strategies for Taipei 101 Financial Center. Journal of Disaster Research, 6: 581–590.
 
N Ding, H Zhang, T Chen, PB Luh, (2014). Evacuees’ behaviors of using elevators during evacuation based on experiments. Transportation Research Procedia, 2: 594–602.
 
JP England, SA Young (1999). Report of the performance of a solid core timber door in a fire test using a standard heating regime. Warrington Fire Research (Aust) Pvt. Ltd.
 
R Howkins (2000). In the Event of Fire—Use Elevators. In: Proceedings of ELEVCON 2000.
 
J Jo, J Lim, S Song, M Yeo, K Kim (2007). Characteristics of pressure distribution and solution to the problems caused by stack effect in high-rise residential buildings. Building and Environment, 42: 263–277.
 
JH Klote, G Tamura (1986). Elevator piston effect and the smoke problem. Fire Safety Journal, 11: 227–233.
 
JH Klote (1991). Design Manual for Smoke Control System, NISTIR 4551. Building and fire research laboratory. National Institute of Standards and Technology.
 
JH Klote (1993). A method for calculation of elevator evacuation time. Journal of Fire Protection Engineering, 5: 83–95.
 
JH Klote, JA Milke (2002). Principles of smoke management. Atlanta, GA, USA: American Society of Heating. Refrigerating and Air-Conditioning Engineers.
 
RS Miller, D Beasley (2009). On stairwell and elevator shaft pressurization for smoke control in tall buildings. Building and Environment, 44: 1306–1317.
 
RS Miller (2011). Elevator shaft pressurization for smoke control in tall buildings: The Seattle approach. Building and Environment, 46: 2247–2254.
 
NFPA (2000). NFPA 92A: Recommended Practice for Smoke control Systems. Quincy, MA, USA: National Fire Protection Association.
 
NFSC (2015). NFSC 501: Fire Safety Standard Codes for Smoke Control System. Ministry of Public Safety and Security, Korea.
 
G Proulx, P Johnson, E Heyes, G Hedman, J Averill, J Pauls, D McColl (2009). The use of elevators for egress: Discussion Panel. In: Proceedings of Human Behaviour in Fire Conference.
 
A Sekizawa, ME Ebihara, H Notake, K Kubota, M Nakano, Y Ohmiya, H Kaneko (1999). Occupants behaviour in response to the high-rise apartments fire in Hiroshima city. In: Proceedings of Human Behaviour in Fire.
 
C Seo, WG Shin (2014). Numerical study on air egress velocity in vestibule pressurization system: Characteristics of air flow in the vestibule with multiple fire doors in an apartment building. Fire Science and Engineering, 28: 30–36.
 
N Shinomiya, S Takada, T Ushio (2015). Study on ventilation in high-rise building based on pressure differences measured at elevator doors. Energy Procedia, 78: 2712–2716.
 
YL Sinai (1999). Comments on the role of leakages in field modelling of under-ventilated compartment fires. Fire Safety Journal, 33: 11–20.
 
KH Sung, HJ Shin, D Baek, HS Ryou (2017). The effect of damper leakage and fire size on the performance of smoke control system in high-rise building. Journal of Mechanical Science and Technology, 31: 4029–4034.
 
Y Wang, F Gao (2004). Tests of stairwell pressurization systems for smoke control in a high-rise building. ASHRAE Transactions, 110(1): 185–193.
 
WJ You, GH Ko, HS Ryou (2014). A study on the unsteady flow characteristics in a vestibule for an injection and pressurization smoke-control system. Fire Safety Journal, 70: 112–120.
Building Simulation
Pages 313-321
Cite this article:
Park Y, Na J, Sung KH, et al. Numerical study on the effect of elevator movement on pressure difference between vestibule and living room in high-rise buildings. Building Simulation, 2019, 12(2): 313-321. https://doi.org/10.1007/s12273-018-0477-1

599