A comparative study of the effects of ventilation-purification strategies on air quality and energy consumption in Beijing, China

Wenjing Ji1Chen Chen2Bin Zhao2,3( )
School of Civil and Resource Engineering, University of Science and Technology Beijing, Beijing 100083, China
Department of Building Science, School of Architecture, Tsinghua University, Beijing 100084, China
Beijing Key Laboratory of Indoor Air Quality Evaluation and Control, Tsinghua University, Beijing 100084, China
Show Author Information

Abstract

In countries suffering from heavy ambient air pollution, ventilation is a problem, as ventilation intakes outdoor air pollutants, such as particulate matter with an aerodynamic diameter less than 2.5 μm (PM2.5), while removing indoor air pollutants. Thus, it is important to identify appropriate ventilation-purification strategies to build healthy indoor environments with low energy consumption. This study reports the comparison of two sets of strategies, i.e., mechanical ventilation with filters and natural ventilation with indoor air cleaners, in respect to energy consumption and the PM2.5 and carbon dioxide (CO2) exposure of occupants in a typical apartment in Beijing, China. A dynamic mass balance model was employed to calculate the PM2.5 and CO2 exposure concentrations, while the energy consumption of heating and cooling was simulated with the Designer’s Simulation Toolkit. It was found that natural ventilation with air cleaners provided lower PM2.5 exposure compared with that of mechanical ventilation with filters; however, mechanical ventilation achieved a lower CO2 exposure concentration. The annual cooling, heating, and fan energy consumption of natural ventilation strategies are lower than those of mechanical ventilation strategies. With respect to natural ventilation, an infiltration rate of 0.3-0.4 h-1 was the preferred setting, which led to low PM2.5 and CO2 exposure with lower energy consumption. The basic requirements for controlling indoor PM2.5 could be met if the threshold is set at 25 μg/m3. The results provide guidelines on how to combine multiple ventilation purification strategies to improve indoor air quality with lower energy usage.

Electronic Supplementary Material

Download File(s)
12273_2020_694_MOESM1_ESM.pdf (1.3 MB)

References

 
ASHRAE (2013). Standard 62.1-2013. Ventilation for Acceptable Indoor Air Quality. Atlanta, GA, USA: American Society of Heating Refrigeration, and Air-Conditioning Engineers.
 
Beijing Municipal Commission of Urban Planning (2012). Design Standard for Energy Efficiency of Residential Buildings DB11/ 891-2012. (in Chinese)
 
Ben-David T, Waring MS (2016). Impact of natural versus mechanical ventilation on simulated indoor air quality and energy consumption in offices in fourteen US cities. Building and Environment, 104: 320-336.
 
Ben-David T, Rackes A, Waring MS (2017). Alternative ventilation strategies in US offices: Saving energy while enhancing work performance, reducing absenteeism, and considering outdoor pollutant exposure tradeoffs. Building and Environment, 116: 140-157.
 
Ben-David T, Waring MS (2018). Interplay of ventilation and filtration: Differential analysis of cost function combining energy use and indoor exposure to PM2.5 and ozone. Building and Environment, 128: 320-335.
 
Berglund B, Brunekreef B, Knöppe H, Lindvall T, Maroni M, et al. (1992). Effects of indoor air pollution on human health. Indoor Air, 2: 2-25.
 
Boxer PA (1990). Indoor air quality: A psychosocial perspective. Journal of Occupational and Environmental Medicine, 32: 425-428.
 
Chen X, Yang H (2018). Integrated energy performance optimization of a passively designed high-rise residential building in different climatic zones of China. Applied Energy, 215: 145-158.
 
Chen C, Zhao Y, Zhao B (2018). Emission rates of multiple air pollutants generated from Chinese residential cooking. Environmental Science & Technology, 52: 1081-1087.
 
Chen J, Brager GS, Augenbroe G, Song X (2019). Impact of outdoor air quality on the natural ventilation usage of commercial buildings in the US. Applied Energy, 235: 673-684.
 
Cho W, Song D, Hwang S, Yun S (2015). Energy-efficient ventilation with air-cleaning mode and demand control in a multi-residential building. Energy and Buildings, 90: 6-14.
 
Ciuzas D, Prasauskas T, Krugly E, Jurelionis A, Seduikyte L, Martuzevicius D (2016). Indoor air quality management by combined ventilation and air cleaning: An experimental study. Aerosol and Air Quality Research, 16: 2550-2559.
 
Cui X, Mohan B, Islam MR, Chou SK, Chua KJ (2017). Energy saving potential of an air treatment system for improved building indoor air quality in Singapore. Energy Procedia, 143: 283-288.
 
Fisk WJ, Rosenfeld AH (1997). Estimates of improved productivity and health from better indoor environments. Indoor Air, 7: 158-172.
 
Fisk WJ (2000). Health and productivity gains from better indoo renvironments and their relationship with building energye fficiency. Annual Review of Energy and the Environment, 25: 537-566.
 
Guo R, Hu Y, Liu M, Heiselberg P (2019). Influence of design parameters on the night ventilation performance in office buildings based on sensitivity analysis. Sustainable Cities and Society, 50: 101661.
 
Han K, Zhang JS, Guo B (2014). A novel approach of integrating ventilation and air cleaning for sustainable and healthy office environments. Energy and Buildings, 76: 32-42.
 
He Y, Liu M, Kvan T, Peng S (2017). An enthalpy-based energy savings estimation method targeting thermal comfort level in naturally ventilated buildings in hot-humid summer zones. Applied Energy, 187: 717-731.
 
Hesaraki A, Myhren JA, Holmberg S (2015). Influence of different ventilation levels on indoor air quality and energy savings: A case study of a single-family house. Sustainable Cities and Society, 19: 165-172.
 
Hong T, Jiang Y (1997). A new multizone model for the simulation of building thermal performance. Building and Environment, 32: 123-128.
 
Hong T, Zhang J, Jiang Y (1997). IISABRE: An integrated building simulation environment. Building and Environment, 32: 219-224.
 
Ji W, Zhao B (2015). Contribution of outdoor-originating particles, indoor-emitted particles and indoor secondary organic aerosol (SOA) to residential indoor PM2.5 concentration: A model-based estimation. Building and Environment, 90: 196-205.
 
Ji W, Li H, Zhao B, Deng F (2018). Tracer element for indoor PM2.5 in China migrated from outdoor. Atmospheric Environment, 176: 171-178.
 
Lam JC, Wan KKW, Tsang CL, Yang L (2008). Building energy efficiency in different climates. Energy Conversion and Management, 49: 2354-2366.
 
Li Y, Chen Z (2003). A balance-point method for assessing the effect of natural ventilation on indoor particle concentrations. Atmospheric Environment, 37: 4277-4285.
 
MacIntosh DL, Minegishi T, Kaufman M, Baker BJ, Allen JG, et al. (2010). The benefits of whole-house in-duct air cleaning in reducing exposures to fine particulate matter of outdoor origin: A modeling analysis. Journal of Exposure Science and Environmental Epidemiology, 20: 213-224.
 
Martins NR, Carrilho da Graça G (2017). Impact of outdoor PM2.5 on natural ventilation usability in California’s nondomestic buildings. Applied Energy, 189: 711-724.
 
Maula H, Hongisto V, Naatula V, Haapakangas A, Koskela H (2017). The effect of low ventilation rate with elevated bioeffluent concentration on work performance, perceived indoor air quality, and health symptoms. Indoor Air, 27: 1141-1153.
 
Ministry of Environment Protection of China (2012). Ambient air quality standards, GB 3095-2012. Beijing: Standards Press of China. (in Chinese)
 
Ministry of Environment Protection of China (2013). Exposure Factors Handbook of Chinese Population: Adult Edition. Beijing: China Environmental Science Press. (in Chinese)
 
Ministry of Housing and Urban-Rural Development of China (2010). Design Standard for Energy Efficiency of Residential Buildings in Severe Cold and Cold Zones. JGJ26-2010. China: Beijing: China Architecture and Building Press. (in Chinese)
 
Oropeza-Perez I, Østergaard PA (2014a). Energy saving potential of utilizing natural ventilation under warm conditions—A case study of Mexico. Applied Energy, 130: 20-32.
 
Oropeza-Perez I, Østergaard PA (2014b). Potential of natural ventilation in temperate countries—A case study of Denmark. Applied Energy, 114: 520-530.
 
Quang TN, He C, Morawska L, Knibbs LD (2013). Influence of ventilation and filtration on indoor particle concentrations in urban office buildings. Atmospheric Environment, 79: 41-52.
 
Rackes A, Waring MS (2013). Modeling impacts of dynamic ventilation strategies on indoor air quality of offices in six US cities. Building and Environment, 60: 243-253.
 
Rackes A, Waring MS (2014). Using multiobjective optimizations to discover dynamic building ventilation strategies that can improve indoor air quality and reduce energy use. Energy and Buildings, 75: 272-280.
 
Rackes A, Waring MS (2017). Alternative ventilation strategies in US offices: Comprehensive assessment and sensitivity analysis of energy saving potential. Building and Environment, 116: 30-44.
 
Rosbach J, Krop E, Vonk M, van Ginkel J, Meliefste C, et al. (2016). Classroom ventilation and indoor air quality—Results from the FRESH intervention study. Indoor Air, 26: 538-545.
 
Sharpe T, Farren P, Howieson S, Tuohy P, McQuillan J (2015). Occupant interactions and effectiveness of natural ventilation strategies in contemporary new housing in Scotland, UK. International Journal of Environmental Research and Public Health, 12: 8480-8497.
 
Shi S, Chen C, Zhao B (2015). Air infiltration rate distributions of residences in Beijing. Building and Environment, 92: 528-537.
 
Shi S, Zhao B (2016). Occupants’ interactions with windows in 8 residential apartments in Beijing and Nanjing, China. Building Simulation, 9: 221-231.
 
Shi S, Chen C, Zhao B (2017). Modifications of exposure to ambient particulate matter: Tackling bias in using ambient concentration as surrogate with particle infiltration factor and ambient exposure factor. Environmental Pollution, 220: 337-347.
 
Standardization Administration of China (2015). Air Cleaner, GB/T 18801-2015. Beijing: Standards Press of China. (in Chinese)
 
Sundell J, Levin H, Nazaroff WW, Cain WS, Fisk WJ, et al. (2011). Ventilation rates and health: Multidisciplinary review of the scientific literature. Indoor Air, 21: 191-204.
 
Sundell J (2004). On the history of indoor air quality and health. Indoor Air, 14: 51-58.
 
Tong Z, Chen Y, Malkawi A (2017). Estimating natural ventilation potential for high-rise buildings considering boundary layer meteorology. Applied Energy, 193: 276-286.
 
Tong Z, Chen Y, Malkawi A, Liu Z, Freeman RB (2016). Energy saving potential of natural ventilation in China: The impact of ambient air pollution. Applied Energy, 179: 660-668.
 
Wang B, Malkawi A (2019). Design-based natural ventilation evaluation in early stage for high performance buildings. Sustainable Cities and Society, 45: 25-37.
 
WHO (2006). Air Quality Guidelines: Global Update 2005: Particulate Matter, Ozone, Nitrogen Dioxide, and Sulfur Dioxide. World Health Organization.
 
Yan D, Xia J, Tang W, Song F, Zhang X, et al. (2008). DeST—An integrated building simulation toolkit Part I: Fundamentals. Building Simulation, 1: 95-110.
 
You R, Cui W, Chen C, Zhao B (2013). Measuring the short-term emission rates of particles in the “personal cloud” with different clothes and activity intensities in a sealed chamber. Aerosol and Air Quality Research, 13: 911-921.
 
Yu T, Heiselberg P, Lei B, Zhang C, Pomianowski M, et al. (2016). Experimental study on the dynamic performance of a novel system combining natural ventilation with diffuse ceiling inlet and TABS. Applied Energy, 169: 218-229.
 
Zhang X, Xia J, Jiang Z, Huang J, Qin R, et al. (2008). DeST—An integrated building simulation toolkit Part II: Applications. Building Simulation, 1: 193-209.
 
Zhao B, Chen C, Zhou B (2018). Is there a timelier solution to air pollution in today's cities? The Lancet Planetary Health, 2: e240.
Building Simulation
Pages 813-825
Cite this article:
Ji W, Chen C, Zhao B. A comparative study of the effects of ventilation-purification strategies on air quality and energy consumption in Beijing, China. Building Simulation, 2021, 14(3): 813-825. https://doi.org/10.1007/s12273-020-0694-2

668

Views

21

Crossref

N/A

Web of Science

23

Scopus

0

CSCD

Altmetrics

Received: 09 June 2020
Accepted: 19 July 2020
Published: 22 August 2020
© Tsinghua University Press and Springer-Verlag GmbH Germany, part of Springer Nature 2020
Return