A numerical study on the effect of column layout on air distribution and performance of column attachment ventilation

Haiguo Yin( )Linna LiRui WuYuanyuan WangAngui Li
School of Building Services Science and Engineering, Xi'an University of Architecture and Technology, Shaanxi, Xi'an 710055, China
Show Author Information

Abstract

Based on the structural characteristics of existing buildings and the disadvantages of current mixed ventilation mode in the application to large space buildings, an original column attachment ventilation (CAV) has been proposed. In this study, the experiment utilized a room space with four columns uniformly distributed in the space to visualize the movement of attached airflow along the cylinder surface and the floor, the numerical technique was employed to study the effects of the column layout (i.e., uniform, centralized, dispersed, and crossed distribution) on the air distribution of CAV mode in a standard four-column full scale model of a shopping mall. Seven indices, including airflow pattern, air diffusion performance index (ADPI), air temperature distribution, heat removal effectiveness, draught rate (DR), predicted mean vote (PMV), and carbon dioxide (CO2) concentration, were used to assess the ventilation performance. In the CAV mode with a uniform column layout scheme, the experimental results indicated that the air supply flows downward along the wall surface, forming a secondary attachment with the ground and spreading along the floor in a fan radiation flow mode. Further, an "air lake" —like speed and temperature distribution similar to displacement ventilation (DV) was formed in the occupied zone. In all simulation cases, it was found that the average air velocity was less than 0.25 m/s in occupied zone, the effectiveness for heat removal was more significant than 1.0, DR value was less than 20%, the PMV level can also satisfy most people. The average CO2 concentration was around 470 ppm in the occupied breathing zone. These results indicated that the CAV mode could be an efficient air distribution method. They demonstrated the technical feasibility of applying the CAV in the space under different column layout schemes.

References

 
Alotaibi S, Chakroun W, Habchi C, Ghali K, Ghaddar N (2019). Influence of mixed and displacement air distribution systems’ design on concentrations of micro-particles emitted from floor or generated by breathing. Journal of Building Engineering, 26: 100855.
 
ASHRAE (2011). ANSI/ASHRAE Standard 70 (RA 2011): Method of Testing the Performance of Air Outlets and Air Inlets. Atlanta: American Society of Heating, Refrigerating, and Air Conditioning Engineers.
 
ASHRAE (2015). ASHRAE Handbook: HVAC Applications. Atlanta: American Society of Heating, Refrigerating, and Air Conditioning Engineers.
 
ASHRAE (2016) ANSI/ASHRAE/IES Standard 90.1: Energy Standard for Buildings Except Low-Rise Residential Buildings. Atlanta: American Society of Heating, Refrigerating, and Air Conditioning Engineers.
 
ASHRAE (2017). ANSI/ASHRAE Standard 55: Thermal Environmental Conditions for Human Occupancy. Atlanta: American Society of Heating, Refrigerating, and Air Conditioning Engineers.
 
Bofah P, Choudhury AK (1985). Modelling and design of nonlinear feedback control law for a large space hoop-column antenna. In: Proceedings of the 24th IEEE Conference on Decision and Control, Fort Lauderdale, FL, USA.
 
Cao G, Nilssen AM, Cheng Z, Stenstad L-I, Radtke A, Skogås JG (2019). Laminar airflow and mixing ventilation: Which is better for operating room airflow distribution near an orthopedic surgical patient? American Journal of Infection Control, 47: 737-743.
 
Causone F, Baldin F, Olesen BW, Corgnati SP (2010). Floor heating and cooling combined with displacement ventilation: Possibilities and limitations. Energy and Buildings, 42: 2338-2352.
 
Chen HJ, Moshfegh B, Cehlin M (2013). Investigation on the flow and thermal behavior of impinging jet ventilation systems in an office with different heat loads. Building and Environment, 59: 127-144.
 
Chen C, Zhao B, Lai D, Liu W (2018). A simple method for differentiating direct and indirect exposure to exhaled contaminants in mechanically ventilated rooms. Building Simulation, 11: 1039-1051.
 
Cheng Y, Fong ML, Yao T, Lin Z, Fong KF (2014). Uniformity of stratum-ventilated thermal environment and thermal sensation. Indoor Air, 24: 521-532.
 
Du Bois D, Du Bois EF (1916). Clinical calorimetry: Tenth paper a formula to estimate the approximate surface area if height and weight be known. JAMA Internal Medicine, 17: 863-871.
 
Du J, Li N (2014) Study on indoor air quality of ceiling radiant cooling panel system integrated with displacement ventilation. In: Proceedings of the 8th International Symposium on Heating, Ventilation and Air Conditioning, Xi’an, China.
 
Etheridge DW, Sandberg M (1996). Building Ventilation: Theory and Measurement. Chichester, UK: John Wiley & Sons.
 
GB/T 18883-2002 (2002). Indoor Air Quality Standard. Beijing: China Standards Press. (in Chinese)
 
Gibson MM, Launder BE (1978). Ground effects on pressure fluctuations in the atmospheric boundary layer. Journal of Fluid Mechanics, 86: 491-511.
 
Han O, Li A, Kosonen R (2019). Hood performance and capture efficiency of kitchens: A review. Building and Environment, 161: 106221.
 
Heiselberg P (2014). Ventilation of large spaces in buildings: Analysis and prediction techniques. IEA Annex 26 Report.
 
ISO (2005). BS EN ISO 7730-2005: Ergonomics of the Thermal Environment—Analytical Determination and Interpretation of Thermal Comfort Using Calculation of the PMV and PPD Indices and Local Thermal Comfort Criteria. Geneva: International Organization for Standardization.
 
Karimipanah T, Awbi HB (2002). Theoretical and experimental investigation of impinging jet ventilation and comparison with wall displacement ventilation. Building and Environment, 37: 1329-1342.
 
Kodur V, MacKinnon D (1998). Simplified design of concrete-filled hollow structural steel columns for fire endurance. Journal of Constructional Steel Research, 46: 298.
 
Li A (2019). Extended Coanda Effect and attachment ventilation. Indoor and Built Environment, 28: 437-442.
 
Liang C, Shao X, Li X (2017). Energy saving potential of heat removal using natural cooling water in the top zone of buildings with large interior spaces. Building and Environment, 124: 323-335.
 
Lin Z, Chow TT, Fong KF, Wang Q, Li Y (2005). Comparison of performances of displacement and mixing ventilations. Part I: thermal comfort. International Journal of Refrigeration, 28: 276-287.
 
Lin Z, Chow TT, Tsang CF (2006). Validation of a CFD model for research into stratum ventilation. International Journal of Ventilation, 5: 345-363.
 
Liu B, Min K, Song J (2015). Effect of thermal plume on personal thermal comfort in displacement ventilation at one side of the room. Procedia Engineering, 121: 1058-1066.
 
Liu Z (2016). Study on air distribution characteristics and design procedures of square column-attached air curtain ventilation. Master Thesis, Xi’an University of Architecture and Technology, China. (in Chinese)
 
Liu J, Dalgo DA, Zhu S, Li H, Zhang L, Srebric J (2019). Performance analysis of a ductless personalized ventilation combined with radiant floor cooling system and displacement ventilation. Building Simulation, 12: 905-919.
 
Mujan I, Anđelković AS, Munćan V, Kljajić M, Ružić D (2019). Influence of indoor environmental quality on human health and productivity - A review. Journal of Cleaner Production, 217: 646-657.
 
Pang P (2013). Research on staggered arrangement wall large space residential system. Advanced Materials Research, 838-841: 2850-2853.
 
Pang P, Sun L (2013). Research on large space residential system. Advanced Materials Research, 838-841: 2846-2849.
 
Satish U, Mendell MJ, Shekhar K, Hotchi T, Sullivan D, et al. (2012). Is CO2 an indoor pollutant? Direct effects of low-to-moderate CO2 Concentrations on human decision-making performance. Environmental Health Perspectives, 120: 1671-1677.
 
Schell M, Int-Hout D (2001). Demand control ventilation using CO2. ASHRAE Journal, 43(2): 18-29.
 
Schmeling D, Bosbach J (2017). On the influence of sensible heat release on displacement ventilation in a train compartment. Building and Environment, 125: 248-260.
 
Sommer K, Kabele K, Kotrbaty M, Petras D, Hojer O (2011). Energy efficient heating and ventilation of large halls. REHVA Guidebook No. 15. Brussels: Federation of European Heating, Ventilation and Air Conditioning Associations.
 
Tang X, Zhong C, Wu L (2014). The research of column base culture in Chinese traditional architectures. Advanced Materials Research, 1065-1069: 2661-2668.
 
Tian L, Lin Z, Wang Q (2010). Comparison of gaseous contaminant diffusion under stratum ventilation and under displacement ventilation. Building and Environment, 45: 2035-2046.
 
Tikka TK, Mirza SA (2009). Equivalent uniform moment diagram factor for structural concrete columns. Canadian Journal of Civil Engineering, 36: 219-240.
 
Versteeg H, Malalasekera W (2007). An Introduction to Computational Fluid Dynamics: The finite Volume Method. Harlow, UK: Pearson Education.
 
Wang Y, Wong KKL, Du H, Qing J, Tu J (2014). Design configuration for a higher efficiency air conditioning system in large space building. Energy and Buildings, 72: 167-176.
 
Wang B, Zhao D, Hui C, Han W, Wang Y (2016). Experimental investigation and analysis on the mechanical behavior of upright column with decorative wings. Steel Construction, 31(10): 34-37. (in Chinese).
 
Wu G, Xue K, Wang J, Li D (2011). Analysis of indoor thermal environment and air-conditioning mode of ventilation in large space building. In: Proceedings of Computer Science for Environmental Engineering and Eco Informatics (CSEEE 2011), Harbin, China.
 
Ye X, Kang Y, Yang F, Zhong K (2019). Comparison study of contaminant distribution and indoor air quality in large-height spaces between impinging jet and mixing ventilation systems in heating mode. Building and Environment, 160: 106159.
 
Yin H, Li A (2016). Study of attached air curtain ventilation within a full-scale enclosure: comparison of four turbulence models. Indoor and Built Environment, 25: 962-975.
 
Yin H, Li A, Liu Z, Sun Y, Chen T (2016). Experimental study on airflow characteristics of a square column attached ventilation mode. Building and Environment, 109: 112-120.
 
Yin H, Wu R, Chen T, Sun Y, Li A (2017). Study on ventilation effectiveness of circular column attached displacement ventilation mode. Procedia Engineering, 205: 3511-3518.
 
Yu J, Cao P, Wu K, Min M (2012). Influence analysis of layout of braces on structural dynamic properties of large space multi-storey buildings. Applied Mechanics and Materials, 226-228: 901-904.
 
Yuan X, Chen Q, Glicksman LR (1999). Models for prediction of temperature difference and ventilation effectiveness with displacement ventilation. ASHRAE Transactions, 105(1): 353-367.
 
Zhang L, Liu X, Zhao K, Jiang Y (2015). Entransy analysis and application of a novel indoor cooling system in a large space building. International Journal of Heat and Mass Transfer, 85: 228-238.
 
Zhang S, Cheng Y, Huan C, Lin Z (2018a). Heat removal efficiency based multi-node model for both stratum ventilation and displacement ventilation. Building and Environment, 143: 24-35.
 
Zhang S, Cheng Y, Huan C, Lin Z (2018b). Modeling non-uniform thermal environment of stratum ventilation with supply and exit air conditions. Building and Environment, 144: 542-554.
 
Zhao K, Liu X, Jiang Y (2016). Application of radiant floor cooling in large space buildings—A review. Renewable and Sustainable Energy Reviews, 55: 1083-1096.
 
Zhu Y (2016). Built Environment. Beijing: China Architecture & Building Press. (in Chinese)
Building Simulation
Pages 1095-1108
Cite this article:
Yin H, Li L, Wu R, et al. A numerical study on the effect of column layout on air distribution and performance of column attachment ventilation. Building Simulation, 2021, 14(4): 1095-1108. https://doi.org/10.1007/s12273-020-0699-x

615

Views

23

Crossref

N/A

Web of Science

25

Scopus

0

CSCD

Altmetrics

Received: 23 December 2019
Accepted: 24 July 2020
Published: 08 September 2020
© Tsinghua University Press and Springer-Verlag GmbH Germany, part of Springer Nature 2020
Return