Comparison study of a novel solid desiccant heat pump system with EnergyPlus

Yu JiangTianshu GeRuzhu Wang( )
Institute of Refrigeration and Cryogenics, Key Laboratory for Power Machinery and Engineering of M.O.E, Shanghai Jiao Tong University, 800 Dongchuan Road, Shanghai 200240, China
Show Author Information

Abstract

The variable refrigerant flow (VRF) air conditioning system usually needs to be operated with a ventilation system, since the VRF system cannot provide fresh air. The commonly used ventilation unit with the VRF system is the heat recovery ventilation (HRV) unit due to its merits of energy saving. In this study, a novel solid desiccant heat pump unit (DESICA) is introduced and mathematical model of DESICA is developed based on the dynamic building energy simulation software—EnergyPlus. The mathematical model is validated with experimental results. Based on the model, performance comparison study is conducted among the novel joint DESICA and VRF (DES&VRF) system, the conventional joint HRV and VRF (HRV&VRF) system, and the original VRF standalone with ventilation (VRFSA) system in an office building in Shanghai. Simulation results show that, HRV&VRF and VRFSA can handle the sensible load, though both of them cannot well deal with the latent load. On the contrary, DES&VRF system can keep both indoor temperature and humidity ratio at the target value, resulting in the best indoor thermal comfort than the other two systems. In addition, through the whole year, DES&VRF consumes 5% more energy than VRFSA and 20% less energy than HRV&VRF.

References

 
TN Aynur, Y Hwang, R Radermacher (2006). Field performance measurements of a VRV AC/HP system. In: Proceedings of 11th International Refrigeration and Air Conditioning Conference, West Lafayette, USA.
 
TN Aynur, Y Hwang, R Radermacher (2008a). Experimental evaluation of the ventilation effect on the performance of a VRV system in cooling mode—Part I: Experimental evaluation. HVAC&R Research, 14: 615-630.
 
TN Aynur, Y Hwang, R Radermacher (2008b). Simulation evaluation of the ventilation effect on the performance of a VRV system in cooling mode—Part II: Simulation evaluation. HVAC&R Research, 14: 783-795.
 
TN Aynur, Y Hwang, R Radermacher (2009). Simulation comparison of VAV and VRF air conditioning systems in an existing building for the cooling season. Energy and Buildings, 41: 1143-1150.
 
TN Aynur, Y Hwang, R Radermacher (2010a). Integration of variable refrigerant flow and heat pump desiccant systems for the heating season. Energy and Buildings, 42: 468-476.
 
TN Aynur, Y Hwang, R Radermacher (2010b). Integration of variable refrigerant flow and heat pump desiccant systems for the cooling season. Applied Thermal Engineering, 30: 917-927.
 
JM Choi, YC Kim (2003). Capacity modulation of an inverter-driven multi-air conditioner using electronic expansion valves. Energy, 28: 141-155.
 
DB Crawley, LK Lawrie, FC Winkelmannc, WF Buhlc, YJ Huang, CO Pedersen, RK Strand, RJ Liesen, DE Fisher, MJ Witte, J Glazer (2001). EnergyPlus: creating a new-generation building energy simulation program. Energy and Buildings, 33: 319-331.
 
DOE (2011). EnergyPlus Documentation: Engineering Reference.
 
N Eskin, H Turkmen (2008). Analysis of annual heating and cooling energy requirements for office buildings in different climates in Turkey. Energy and Buildings, 40: 763-773.
 
W Goetzler (2007). Variable refrigerant flow systems. ASHRAE Journal, 49(4): 24-31.
 
X Hai, S Jun, Z Hang, TC Bin (2006). Design and research of the digital VRV multi-connected units with three pipes type heat recovery system. In: Proceedings of 11th International Refrigeration and Air Conditioning Conference, West Lafayette, USA.
 
SC Hu, RH Yang (2005). Development and testing of a multi-type air conditioner without using AC inverters. Energy Conversion and Management, 46: 373-383.
 
YM Li, JY Wu, S Shiochi (2009). Modeling and energy simulation of the variable refrigerant flow air conditioning system with water-cooled condenser under cooling conditions. Energy and Buildings, 41: 949-957.
 
YM Li, JY Wu, S Shiochi (2010a). Experimental validation of the simulation module of the water-cooled variable refrigerant flow system under cooling operation. Applied Energy, 87: 1513-1521.
 
YM Li, JY Wu, S Shiochi (2010b). Energy simulation and analysis of the heat recovery variable refrigerant flow system in winter. Energy and Buildings, 42: 1093-1099.
 
JL Lin, TJ Yeh (2007). Identification and control of multi-evaporator air conditioning systems. International Journal of Refrigeration, 30: 1374-1385.
 
X Liu, T Hong (2010). Comparison of energy efficiency between variable refrigerant flow systems and ground source heat pump systems. Energy and Buildings, 42: 584-589.
 
YC Park, MK Min (2001). Performance analysis on a multi-type inverter air conditioner. Energy Conversion and Management, 42: 1607-1621.
 
M Shahrestani, R Yao, GK Cook (2013). Developing new components for variable flow distribution system modelling in TRNSYS. Building Simulation, 6: 309-322.
 
W Shi, S Shao, X Li, X Peng, X Yang (2003). A network model to simulate performance of variable refrigerant volume refrigeration systems. ASHRAE Transactions, 109(2): 61-68.
 
C Wu, Z Xingxi, D Shiming (2005). Development of control method and dynamic model for multi-evaporator air conditioners. Energy and Conversion, 46: 451-465.
 
K Zhong, YM Kang (2009). Applicability of air-to-air heat recovery ventilators in China. Applied Thermal Engineering, 29: 830-840.
 
YP Zhou, JY Wu, RZ Wang, S Shiochi (2007). Energy simulation in the variable refrigerant flow air-conditioning system under cooling conditions. Energy and Buildings, 39: 212-220.
 
YP Zhou, JY Wu, RZ Wang, S Shiochi, YM Li (2008). Simulation and experimental validation of the variable-refrigerant-volume (VRV) air-conditioning system in EnergyPlus. Energy and Buildings, 40: 1041-1047.
Building Simulation
Pages 467-476
Cite this article:
Jiang Y, Ge T, Wang R. Comparison study of a novel solid desiccant heat pump system with EnergyPlus. Building Simulation, 2014, 7(5): 467-476. https://doi.org/10.1007/s12273-014-0166-7